ALL products

C 33-224 / C33-225

C 33-224 / C33-225 are MV cable. It is Stranded Bare or Tinned Copper Conductor, XLPE Insulation, Copper Tape Shielded Airport Lighting Cable

C-33-224--C33-225.jpg

Applications

C 33-224 / C33-225 cables are used as airfield lighting equipment primary cables for the series circuit connecting the Constant Current Regulators and the isolating transformers, and between the isolating transformers.

Standards

C33-224

C33-225

Construction

Conductor: Stranded bare or tinned copper conductor.

Inner Semi-Conductor: Extruded semi-conducting compound.

Insulation: XLPE/MDPE

Outer Semi-Conductor: Extruded semi-conducting compound.

Shield: Copper tape shield or Copper wire shield. 

Sheath: XLPE/PVC/HFFR/CR


Technical Data

Rated Voltage Uo/U (Um)3.6/6(7.2kV); 6/10 (12kV)
Maximum Conductor Temperature90℃
Short Circuit Temperature250℃
Operating Temperatures-20℃~+70℃
Minimum Bending Radiusstatic: 10×OD; dynamic: 20×OD
Impacted ResistantYes
Weather ResistantYes


Dimensions and Weight

3.6/6 (7.2kV)

ConstructionNo. of StrandNominal Insulation ThicknessNominal Sheath ThicknessNominal Overall DiameterNominal Weight
No. ×mm²-mmmmmmkg/km
1×672.71.412.5198

6/10 (12kV)

ConstructionNo. of StrandNominal Insulation ThicknessNominal Sheath ThicknessNominal Overall DiameterNominal Weight
No. ×mm²-mmmmmmkg/km
1×673.61.614.7250